8 Digital Input Module 
Cdios 6153 

Command / Reply / Event messages V2.5
New or up-date devices are visible marked V2.x 

 

  Cdios Controller Commands  |  Cdios Firmware Page

6153 Cdios Module V1.0  |  6153 Cdios Module V1.1  |  6153 Cdios Module V2.0

Addition to V2.0:

  • Internal programming software updated for Micro-Controller update. V2.5 up runs in all modules, <V2.5 cannot run in newer hardware

All Cdios messages are presented as 8 bytes long. When variable length messages are selected, the part of the message that is not send over the CAN bus is represented in italic/light gray text.


Command code 08h: Read inputs

This commands reads the 8 inputs, latched inputs or change flags.

Command

Module ID

3

4

5

6

7

8

08h

0 - 15

Selector

0

0

0

0

0


Parameter

Value

Description

Selector

0

Read 8 inputs directly

1

Read latched inputs, latched by the latest SYNC command

2

Read change flags (and clear them after the read).

A change flag is set when an input changes from it's inactive to active state (from 0 to 1).

The change flags can be used when the use of the change of state event produces too much messages...

Normal reply is:
 

Reply

Module ID

3

4

5

6

7

8

08h

0 - 15

Selector

Data

0

0

0

0


Parameter

Bit

Description

Selector x Copy of value of the command

Data

0

bit 0 contains the state of input 1, 0 is inactive, 1 is active

until

bit ....

7

bit 7 contains the state of input 8, 0 is inactive, 1 is active


 Possible error message:

Error

Module ID

3

4

5

6

7

8

88h

0 - 15

0

0

Error Status

0

0

0


Parameter

Bit

Description

Error status

0

1 =  Selector parameter out of range

 


Command code 09h: Set event on input change mask

This command defines the inputs to scan for 'change of state'.
 

Command

Module ID

Selector

4

5

6

7

8

09h

0 - 15

00h

Mask

0

0

0

0


Parameter

Bit

Default

Description

Mask

0

0

when 1 it enables scanning input 1 for change

until

 

when ...

7

0

when 1 it enables scanning input 8 for change

Confirmation reply message (suppressed when 'Confirm' is 0):
 

Reply

Module ID

3

4

5

6

7

8

09h

0 - 15

0

0

0

0

0

0

Possible error message:

Error

Module ID

3

4

5

6

7

8

89h

0 - 15

0

0

Error Status

0

0

0


Parameter

Bit

Description

Error status

0

1 =  Selector parameter out of range


Command code 09h: Read event on input change mask

This commands reads the inputs to scan for 'change of state'.
 

Command

Module ID

Selector

4

5

6

7

8

09h

0 - 15

80h

0

0

0

0

0


Normal reply is:
 

Reply

Module ID

Selector

4

5

6

7

8

08h

0 - 15

80h

Mask

0

0

0

0


Parameter

Description

Mask

Same format as in the 'Set event on input change mask' command

Possible error message:

Error

Module ID

3

4

5

6

7

8

89h

0 - 15

0

0

Error Status

0

0

0


Parameter

Bit

Description

Error status

0

1 =  Selector parameter out of range


Command code 0Ah: Set Response Delay time

This commands configures the input Response Delay counters.

 

Command

Module ID

Group

4

5

6

7

8

0Ah

0 - 15

00h

Response Delay 1

Response Delay 2

Response Delay 3

Response Delay 4

0

01h

Response Delay 5

Response Delay 6

Response Delay 7

Response Delay 8

0

 

Parameter

Value

Default

Description

Response Delay 1-8

0-255

0

range is 0 - 255 milliseconds (0 is no Response Delay)

Confirmation reply message (suppressed when 'Confirm' is 0):

 

Reply

Module ID

3

4

5

6

7

8

0Ah

0 - 15

0

0

0

0

0

0

Possible error message:

 

Error

Module ID

3

4

5

6

7

8

8Ah

0 - 15

0

0

Error Status

0

0

0


Parameter

Bit

Description

Error status

0

1 =  Group parameter out of range

 


Command code 0Ah: Read Response Delay time

This command gets the configuration of the input Response Delay counters.
 

Command

Module ID

Group

4

5

6

7

8

0Ah

0 - 15

80h/81h

0 0 0 0

0

 Normal reply is:

Reply

Module ID

Group

4

5

6

7

8

0Ah

0 - 15

80h

Response Delay 1

Response Delay 2

Response Delay 3

Response Delay 4

0

81h

Response Delay 5

Response Delay 6

Response Delay 7

Response Delay 8

0

 

Parameter

Description

Response Delay 1-8

Same format as in the 'Set response delay time' command

Confirmation reply message (suppressed when 'Confirm' is 0):
 

Reply

Module ID

3

4

5

6

7

8

0Ah

0 - 15

0

0

0

0

0

0

Possible error message:
 

Error

Module ID

3

4

5

6

7

8

8Ah

0 - 15

0

0

Error Status

0

0

0


Parameter

Bit

Description

Error status

0

1 =  Group parameter out of range

 


Command code 05h: Store configuration

This command stores the current or the default I/O module configuration into internal EEPROM memory.
The configuration is restored from this memory after power on or a reset command.

Command

Module ID

3

4

5

6

7

8

05h

0 - 15

Selector

43h

44h

53h

0

0


Parameter

Value

Description

Selector

0

Store current configuration

1

Change configuration into default and then store it.

The internal EEPROM erasing / programming takes 120 up to 250 milli-seconds, then the reply message is send.
During programming I/O communication with this module is inhibited.

Sending a command will result in a general error message with errorcode = 8.

The confirmation reply message for this command is NEVER SUPPRESSED.

Reply

Module ID

3

4

5

6

7

8

05h

0 - 15

0

0

0

0

0

0


 Possible error message:

 

Error

Module ID

3

4

5

6

7

8

85h

0 - 15

0

0

Error Status

0

0

0


Parameter

Bit

Description

Error status

0

1 =  Selector parameter out of range

1 1 = 'password' bytes 4-6 in command are not equal to 43h,44h,53h
2 1 = Configuration EEPROM programming error
 


Events

A 'change of State' event can be configured with the 'Set event on input change mask' command.
If an enabled input changes state, a read input event message is sent:

 

Event

Module ID

3

4

5

6

7

8

48h

0 - 15

0

Data

0

0

0

0


Parameter

Bit

Description

Data

0

bit 0 contains the state of input 1, 0 is inactive, 1 is active

until

bit ....

7

bit 7 contains the state of input 8, 0 is inactive, 1 is active

All data is stored in one byte, so the application has to find out itself which input actually changed.

Input change events react directly on the actual inputs, not on latched inputs, and have nothing to do with the change flags.


Home | Cdios