Supply |
Conditions |
Min. |
Typ. |
Max. |
Units |
|---|---|---|---|---|---|
|
Supply power |
Serial no < 121xxxxx |
23 |
24 |
25 |
Vdc |
|
|
12 | - | 28 | ||
|
Power consumption |
Serial no < 121xxxxx |
- |
1.5 |
2.5 |
W |
|
|
0.8 | 1 | |||
| Power on Current | During power on | - | 105 | - | mA |
|
Fuse slow |
|
- |
1 |
- |
A |
|
Input |
Conditions |
Min. |
Typ. |
Max. |
Units |
|---|---|---|---|---|---|
|
No. Inputs |
Isolated to Cdios |
- |
8 |
- |
pcs |
|
Voltage |
Serial no < 121xxxxx |
- |
24 |
30 |
Vdc |
| 12 |
- |
28 | |||
|
Switch threshold |
Serial no < 121xxxxx |
7 |
- |
17 |
Vdc |
| 5 |
- |
9.5 | |||
|
PNP/NPN resistance |
via jumper |
- |
4.4 |
- |
kOhm |
|
Debounce time |
Software adjustable |
0 |
- |
255 |
ms |
|
Excitation voltage |
see supply power |
- |
- |
- |
Vdc |
|
Connectors |
Type |
|---|---|
|
Power supply |
2 pole screw/plug connector |
|
Input 1-4 |
6 pole screw/plug connector (Gnd, V, 1, 2, 3, 4) |
|
Input 5-8 |
6 pole screw/plug connector (Gnd, V, 5, 6, 7, 8) |
|
Cdios bus |
10 pole Flatcable female |
|
10 pole Flatcable male |
|
Signaling LEDs |
Color |
Text |
|
On each input |
Red |
Active |
|
General |
Conditions |
Min. |
Typ. |
Max. |
Units |
|---|---|---|---|---|---|
|
I/O module |
Controlled by Cdios controller |
- |
- |
- |
- |
|
Module select |
via 4 dipswitches |
- |
- |
- |
- |
|
MPU |
Motorola 68HC908 |
- |
8 |
- |
Mc |
|
MPU watchdog |
- |
- |
52 |
- |
ms |
|
MTBF |
T amb..=40°C |
- |
87000 |
- |
h |
|
Warranty |
- |
- |
2 |
- |
year |
|
Environmental |
Conditions |
Min. |
Typ. |
Max. |
Units |
|---|---|---|---|---|---|
|
Operating temperature |
- |
-20 |
- |
70 |
°C |
|
Storage temperature |
- |
-25 |
- |
80 |
°C |
|
Relative humidity |
at 40°C non Cond. |
- |
- |
90 |
% |
|
Burn in cycle |
25°C .. -25°C .. 60°C |
- |
1 |
- |
cycle |
|
Physical |
|
|---|---|
|
Housing |
35 mm DIN rail |
|
Dimensions L * W * H |
96 * 61 * 55 mm (incl. rail) |
|
Color |
Light Grey |
|
Protection class |
IP32 |
|
Weight |
101 g |
|
Conformity |
|
|---|---|
|
EN 50081-1 |
Electromagnetic compatibility -Generic emission standard- Residential, commercial and light industry environment |
|
EN 50081-2 |
Electromagnetic compatibility -Generic emission standard- Industrial environment |
|
EN 50082-1 |
Electromagnetic compatibility -Generic immunity standard-Residential, commercial and light industry environment |
|
EN 50082-2 |
Electromagnetic compatibility -Generic immunity standard- Industrial environment |
|
EN 55022 |
Emits and methods of measurement of radio disturbance characteristics of information technology equipment |
|
EN 61010-1 |
Safety requirements for electrical equipment for measurement, control and laboratory use |
| Home | Last Modified: 1 February 2004 |