Digital Output Module
Cdios 6156

 

The high-lights on this module

Click for full size picture

  • About the Module
    • Small DIN rail device
    • I/O device of the CD systems Input Output System
    • Controlled by the Cdios Controller
      • Up to16 Cdios Modules can be connected to one controller
    • Low Cost device.
    • This Module must be connected to a Cdios Controller.
  • About the Outputs
    • 8 Digital Outputs
      • Electrically Isolated
      • Output voltage is supply voltage   
      • Max 1A output
      • One shot timer 0-65535 ms
      • Open loop detection
      • Short circuit detection
      • LED indication
  • About the Cdios Commands
    • Write data output
    • Write data in output latch (output on Sync Command)
    • Configure One-shot time on each output
    • Configure Event message on error
    •  Read output status of each output
      • Output state
      • Short Circuit
      • No load
      • Over temperature > 145°C
      • Over voltage >35V
  • About the Power supply
    • Switched regulator 
    • low consumption
    • 12 ...28 Vdc supply voltage range
  • About the Housing
    • Small size 96 x 61 x 50 mm
    • DIN rail socket
  • About the Connections
    • I/O via detachable screw connectors
    • 10-wire Flatcable connection to previous module
    • 24Vdc power via detachable screw connectors
  • About the Application areas
    • Measurement- and control equipment,
    • Process- and Machine Control Systems,
    • Greenhouse and Agro industries.

 


Diagram 6156 

 


Connections 6156 

 


Connections Table 6156

 

pin name Description
1 Gnd Supply Ground
2 Vmpu Supply Power  12...28Vdc
2b Vpwr Supply power 12...28Vdc

Remark: serial no <121xxxxx : 24Vdc device

Remark: serial no <144xxxxx : 2b = 2, one connection

3 Gnd Ground, equal to supply ground
4 Out 1 0= Gnd, 1= Vpwr
5 Out 2 0= Gnd, 1= Vpwr
6 Gnd Ground, equal to supply ground
7 Out 3 0= Gnd, 1= Vpwr
8 Out 4 0= Gnd, 1= Vpwr
9 Gnd Ground, equal to supply ground
10 Out 5 0= Gnd, 1= Vpwr
11 Out 6 0= Gnd, 1= Vpwr
12 Gnd Ground, equal to supply ground
13 Out 7 0= Gnd, 1= Vpwr
14 Out 8 0= Gnd, 1= Vpwr
 

Short Function Description 6156

 

Write outputs (direct, latched, one-shot, one-shot latched, Set / Clear output)
Read output status (status, short circuit, noload, over temperature, over voltage)
Set event mask (status, short circuit, noload, over temperature, over voltage)
Set output one shot timers (separate time on each output)
 