8 Digital Output Module
|
|
Supply |
Conditions |
Min. |
Typ. |
Max. |
Units |
|---|---|---|---|---|---|
|
Supply power |
Serial no < 121xxxxx |
23 |
24 |
25 |
Vdc |
|
|
12 | - | 28 | ||
|
Power consumption |
Serial no < 121xxxxx |
- |
1 |
2.5 |
W |
|
|
- | 0.4 | 0.7 | ||
| Power on Current | During power on | - | 117 | - | mA |
|
Fuse slow |
|
- |
8 |
- |
A |
|
Output |
Conditions |
Min. |
Typ. |
Max. |
Units |
|---|---|---|---|---|---|
|
No. of outputs |
Isolated to Cdios bus |
- |
8 |
- |
pcs |
|
Voltage |
see supply power |
- |
- |
- |
Vdc |
|
Load current |
Individual |
- |
0.75 |
1.5 |
A |
|
Total current group 1-4 or 5-8 |
- |
- |
- |
2 |
A |
|
On resistance |
current 1A |
- |
0.8 |
1.3 |
Ohm |
| Minimum load to prevent
no-load error |
Internal pull-up: 50K 12V supply 24V supply |
- | 25 10 |
- | kOhm |
| Short circuit current (note) | Individual. 12V supply 24V supply |
|
|
|
A |
| Short circuit duration (note) | Individual. Ambient temperature 25 degrees C |
- |
150 |
- |
ms |
| Note: Current limiting is performed by limiting the power dissipation of the
output switches to 15W, so short circuit current is higher when the voltage
across switch is lower. When the short circuit lasts, the internal temperature of the output switch will rise and the software will switch off the short-circuited outputs. Capacitive loads. When the output is loaded with a large capacity (200 uF or more), the
software may report a 'short-circuit' when the output is switched on and the
capacity isn't charged above 4 Volts within 5 milli-seconds. |
|
Connectors |
Type |
|---|---|
| Power supply | 2 pole screw/plug connector |
| Output 1-4 | 6 pole screw/plug connector (Gnd, V, 1, 2, 3, 4) |
| Output 5-8 | 6 pole screw/plug connector (Gnd, V, 5, 6, 7, 8) |
| Cdios bus | 10 pole Flatcable female |
| 10 pole Flatcable male |
| Signaling LEDs | Color | Text |
| On each input | Red | Active |
|
General |
Conditions |
Min. | Typ. | Max. | Units |
|---|---|---|---|---|---|
| I/O module | Controlled by Cdios controller |
- |
- | - | - |
| Module select | via 4 dipswitches | - | - | - | - |
| MPU | Motorola 68HC908 | - | 8 | - | Mc |
| MPU watchdog | - | - | 52 | - | ms |
| MTBF | T amb..=40°C | - | 87000 | - | h |
| Warranty | - | - | 2 | - | year |
|
Environmental |
Conditions |
Min. | Typ. | Max. | Units |
|---|---|---|---|---|---|
| Operating temperature | - | -20 | - | 70 | °C |
| Storage temperature | - | -25 | - | 80 | °C |
| Relative humidity | at 40°C non Cond. | - | - | 90 | % |
| Burn in cycle | 25°C .. -25°C .. 60°C | - | 1 | - | cycle |
|
Physical |
|
|---|---|
| Housing | 35 mm DIN rail |
| Dimensions L * W * H | 96 * 61 * 55 mm (incl. rail) |
| Color | Light Grey |
| Protection class | IP32 |
| Weight | 101 g |
|
Conformity |
|
|---|---|
| EN 50081-1 | Electromagnetic compatibility -Generic emission standard- Residential, commercial and light industry environment |
| EN 50081-2 | Electromagnetic compatibility -Generic emission standard- Industrial environment |
| EN 50082-1 | Electromagnetic compatibility -Generic immunity standard-Residential, commercial and light industry environment |
| EN 50082-2 | Electromagnetic compatibility -Generic immunity standard- Industrial environment |
| EN 55022 | Emits and methods of measurement of radio disturbance characteristics of information technology equipment |
| EN 61010-1 | Safety requirements for electrical equipment for measurement, control and laboratory use |
| Home | Last Modified: 1 February 2006 |