Pt100 Input Module
Cdios 6162

Technical Specifications

 

Supply

Conditions

Min.

Typ.

Max.

Units

Supply power

 
12 - 28 Vdc

Power consumption

 
- 0.9 1.3 W
Power on Current During power on - 130 - mA

Fuse slow

auto reset

-

0.2

-

A

 

Input Volt

Conditions

Min.

Typ.

Max.

Units

No. Inputs

Isolated to bus

-

3

-

pcs

Range

-

-200
-328

-

+819
+1506

°C
°F

Wire systems

3-wire or 4-wire

-

-

-

-

Max. wire resistance 4-wire measurement
3-wire measurement (wire resistances must be equal within 0.03 Ohms for 0.1°C accuracy)
- - 100
30
Ohms
Ohms

Resolution

lowest sample rate

-

0.025
0.05

-

°C
°F

Accuracy

Ambient temperature 25°C,
lowest sample rate

-

0.05
0.1

0.1
0.2

°C
°F

Non-linearity

-

-

-

0.01
0.02

°C
°F

Impedance

-

-

10

-

M Ohm

Excitation current

-

-

0.2

-

mA

Over voltage protection

-

-

60

-

Vdc

Line rejection

50/60 Hz

80

-

100

dB

Temperature drift

-

1

6

10

ppm/°C

 
Sample interval times / resolution
Sample rate config value 1 input 2 inputs 3 inputs effective resolution
0 - 2 10 ms 20 ms 30 ms 0.4°C / 0.8°F
4 - 6 20 ms 40 ms 60 ms 0.1°C / 0.2°F
  8 - 10 33 ms 67 ms 100 ms 0.025°C / 0.05°F
12 - 14 40 ms 80 ms 120 ms 0.025°C / 0.05°F
 
Moving Average filter Full-Scale step response time
Filter setting samples averaged 1 input @ highest sample rate 3 inputs @ lowest sample rate
0 1 10 ms 120 ms
1 2 20 ms 240 ms
2 4 40 ms 480 ms
3 8 80 ms 960 ms
4 16 160 ms 1920 ms
 

Connectors

Type

Power supply

2 pole screw/plug connector

Input 1-3

4 pole screw/plug connector (Gnd, InL, InH, Vex)

Cdios bus

10 pole Flatcable female

10 pole Flatcable male

 

Signaling LEDs

Color

Text

n.a.

n.a.

n.a.

 

General

Conditions

Min.

Typ.

Max.

Units

I/O module

Controlled by Cdios controller

-

-

-

-

Module select

via 4 dipswitches

-

-

-

-

MPU

Motorola 68HC908

-

8

-

Mc

MPU watchdog

-

-

52

-

ms

MTBF

T amb..=40°C

-

87000

-

h

Warranty

-

-

2

-

year

 

Environmental

Conditions

Min.

Typ.

Max.

Units

Operating temperature

-

-20

-

70

°C

Storage temperature

-

-25

-

80

°C

Relative humidity

at 40°C non Cond.

-

-

90

%

Burn in cycle

25°C .. -25°C .. 60°C

-

1

-

cycle

 

Physical

Housing

35 mm DIN rail

Dimensions L * W * H

96 * 61 * 55 mm (incl. rail)

Color

Light Grey

Protection class

IP32

Weight

104 g

 

Conformity

EN 50081-1

Electromagnetic compatibility -Generic emission standard- Residential, commercial and light industry environment

EN 50081-2

Electromagnetic compatibility -Generic emission standard- Industrial environment

EN 50082-1

Electromagnetic compatibility -Generic immunity standard-Residential, commercial and light industry environment

EN 50082-2

Electromagnetic compatibility -Generic immunity standard- Industrial environment

EN 55022

Emits and methods of measurement of radio disturbance characteristics of information technology equipment

EN 61010-1

Safety requirements for electrical equipment for measurement, control and laboratory use


Home