RS232 / CAN port 
type 6393, version 1.02

Technical Specifications

 

Supply

Conditions

Min.

Typ.

Max.

Units

Supply power

Via 2-pole connector and
5-pole CAN connector

10

-

36

Vdc

Power consumption

-

-

1.5

2

W


RS232

Conditions

Min.

Typ.

Max.

Units

RS232 type

electrically isolated RS232-C

-

-

-

-

Baudrate

Selectable

1200

9600

38400

Baud

Stop bit

Fixed

-

1

-

bit

Handshake

RTS/CTS

-

-

-

-

CAN to RS232 buffer 1024 bytes 100 - 500 CAN messages
RS232 to CAN buffer RTS output inactive when 2 messages pending - 3 - CAN messages

General

Conditions

Min.

Typ.

Max.

Units

MPU

Motorola 68HC908AZ60

-

10

-

Mc

Memory

Flash Eprom

-

64

-

kb

MPU watchdog

-

-

84

-

ms

MTBF

T amb.=40°C

-

87.000

-

h

Configuration

via CAN-bus

-

-

-

-

Warranty

-

-

2

-

year


CAN-bus

Conditions

Min.

Typ.

Max.

Units

CAN chip set

HC908AZ60
PCA82C251T 

-

-

-

-

Bit rate timing table

Selectable

10

-

1000

kbit

Protocol

CAN V 2.0a

-

-

-

-

Application layer

Special CAN port Function

-

-

-

-


Environmental

Conditions

Min.

Typ.

Max.

Units

Operating temperature

-

-20

-

70

°C

Storage temperature

-

-25

-

80

°C

Relative humidity

at 40°C non Cond.

-

-

90

%

Burn in cycle

25°C .. -25°C .. 60°C

-

1

-

cycle


Connectors

No.

Type

Power 1 2-pole combicon

CAN Comm. Connectors

2

4 pole data communication connector RJ10

1 5-pole combicon

RS232 connector

-

9-pole sub-D female

Connecting details

-

On Internet


Signaling LEDs

No.

Color

Text

CAN communication

2

Red

Bus active /Node active

I/O

4

Red

TXD, RXD, RTS, CTS


Physical

Housing

Grey Polystyrol

Dimensions L * W * H

99 * 61 * 55 mm (incl. rail)

Protection class

IP32

Weight

156 g


Conformity

EN 50081-1

Electromagnetic compatibility -Generic emission standard- Residential, commercial and light industry environment

EN 50081-2

Electromagnetic compatibility -Generic emission standard- Industrial environment

EN 50082-1

Electromagnetic compatibility -Generic immunity standard-Residential, commercial and light industry environment

EN 50082-2

Electromagnetic compatibility -Generic immunity standard- Industrial environment

EN 55022

Limits and methods of measurement of radio disturbance characteristics of information technology equipment

EN 61010-1

Safety requirements for electrical equipment for measurement, control and laboratory use

ISO 11989

CAN for high-speed communication

 